Requirement: 6.1.3.6.6 Floor Opening Protection Adjacent to Escalator
Wellway
Floor openings adjacent to the entire length of the escalator
wellway shall be provided with protection in accordance with
the applicable building code.
It is important to understand that this requirement means that
the length of the wellway, from top to bottom must be protected.
This is not stipulating how to protect the upper or lower ends
of an escalator as they pierce a floor to another landing.
These two sketches illustrate the point:

The area between the arrows above needs to be protected in accordance
with local building codes. What this means is that a handrail or
other means of protecting people from falling over the side of
the escalator (with a lower handrail height limited to a maximum
height of 1m).
This rule came about during harmonization with the Canadian B44
elevator/escalator code as a result of fatalities in Canada and
in the United States. This requirement will be difficult in certain
atrium installations in malls, retail stores, hotels, airports,
and transit applications. Protection similar to what we illustrate
below will be required. This sketch illustrates two key points:

- Where the handrail or balustrade would need to be installed.
- You can’t connect to the escalator itself to provide
this balustrade or handrail. There is not a single escalator
manufacturer that we have found that will permit this type of
protection to be attached to their escalator.
The rules within the A17.1 Code are intended to be clear and unambiguous,
but there are often unintended consequences to the rules that leave
the reader confused as to the intention of the Code. Each subcommittee
of A17.1 addresses interpretations at their regular meetings before
any new business to help assure a prompt and responsive clarification.
For example, in 2004 a request for interpretation was submitted
on this requirement. A question came up from a designer who thought
that the intent was to protect the escalator wellway at the top
landing only. Another designer on the same project felt that the
wording required the protection of the opening along the inclined
portion of the escalator. This is an important distinction because
long escalators could have 50 to 100 more feet of handrails. Couple
this requirement with the riddle of how to support that handrail
and it is easy to see that a clear interpretation was required.
The request for interpretation became Inquiry 03-44 and was first
submitted on July 24, 2003. The committee met and discussed the
rule at length at the regularly scheduled meeting in October 2003.
The subcommittee was unable to come to a resolution so the inquiry
was postponed until the next meeting in February 2004.
Upon further consideration, and a lot more discussion and debate,
the subcommittee approved a response that the rule does require
protection along the full length of the wellway. The Standards
Committee approved that response unanimously in May 2004.
This rule and subsequent clarification has a significant impact
on building designs with escalators. This is not work that the
escalator manufacturer is going to do. Each building design with
an escalator that is not directly against a wall will require protection
of some significance.
Most malls, department stores, airports, and sports facilities
will be affected by this new rule. We hope that this column helps
shed light on this new requirement and how it may affect your project!  |